Demand Control Ventilation

In stock
$0.00

This incentive is available for the installation of CO2 sensor controls to modulate the amount of outside air intake based on actual occupancy levels.


Out Of Stock

You have a saved application!

Required Documentation:
  • Floor plans and controlled area: Detailed plans highlighting the areas where occupancy sensors will be installed and the zones they will control.
  • HVAC documentation (e.g., BAS graphic screenshot, control programming, sequence of operations, functional testing documentation).
  • Pre- and post-installation data: Documentation showing the minimum outside air setpoint before and after the installation of CO2 sensors, ensuring that the post-installation setpoint is adjusted based on CO2 levels and is lower than the existing case, alongside evidence of a functioning economizer.
  • Applicability: Eligible for both retrofit projects and new construction (if not mandated by code).
  • Baseline Efficiency:
    • The existing HVAC system must either have fully functioning air-side economizers or undergo economizer repairs as part of the implementation of DCV.
    • The minimum outside air damper position setpoint should be ≥10 percent of the supply air when the space is occupied, in compliance with the current ASHRAE 62 standard or applicable local building codes.
  • Qualifying Efficiency Requirement: The installed CO2 sensor must effectively control the minimum percentage of the outside air intake, reducing it below the existing setpoint based on real-time occupancy levels.
  • Exclusions:
    • Cannot be combined with incentives for economizers.
    • DCV mandated by code for new construction.