RCx Demand Control Ventilation

In stock
$0.00

This incentive is available for installing CO2 sensor controls to modify the percentage of outside air based on variable occupancy levels.


Out Of Stock

You have a saved application!

  • Conditioned space must be kept between 65˚F and 75˚F during operating hours.
  • System must have current fresh air requirements ≥10 percent of supply air requirements.
  • CO2 sensors must be installed in conjunction with fully functioning air-side economizers.
  • Dual-temperature air-side economizers with zone-level CO2 sensors for rooftop units qualify.
  • Return system CO2 sensors are required for built-up systems.
  • Controlled space must meet the minimum requirements of the current ASHRAE 62 standard, as well as all local building codes and manufacturers recommendations.
  • CO2 must control the outside air or VAV air dampers.
  • The incentive is calculated per square foot of area controlled.
  • Floor plans and controls schedules must be submitted with the application.
Retro-commissioning only:
  • All above requirements apply except the DCV control is not working optimally.
  • Existing - Must submit documentation (e.g. EMS screenshots, sequence of operations, functional testing documentation) showing sensor not used to reduce VAV damper position (and thus AHU fan speed) and/or outside air damper position beyond minimum in existing case.
  • Proposed - Must submit documentation showing sensor used to reduce VAV damper position and/or outside air damper position beyond minimum in proposed case.