RCx Demand Control Ventilation

In stock

This incentive is available for installing CO2 sensor controls to modify the percentage of outside air based on variable occupancy levels.


Out Of Stock

You have a saved application!

  • Conditioned space must be kept between 65˚F and 75˚F during operating hours.
  • System must have current fresh air requirements ≥10 percent of supply air requirements.
  • CO2 sensors must be installed in conjunction with fully functioning air-side economizers.
  • Dual-temperature air-side economizers with zone-level CO2 sensors for rooftop units qualify.
  • Return system CO2 sensors are required for built-up systems.
  • Controlled space must meet the minimum requirements of the current ASHRAE 62 standard, as well as all local building codes and manufacturers recommendations.
  • CO2 must control the outside air or VAV air dampers.
  • The incentive is calculated per square foot of area controlled.
  • Floor plans and controls schedules must be submitted with the application.
Retro-commissioning only:
  • All above requirements apply except the DCV control is not working optimally.
  • Existing - Must submit documentation (e.g. EMS screenshots, sequence of operations, functional testing documentation) showing sensor not used to reduce VAV damper position (and thus AHU fan speed) and/or outside air damper position beyond minimum in existing case.
  • Proposed - Must submit documentation showing sensor used to reduce VAV damper position and/or outside air damper position beyond minimum in proposed case.